Tripp Lite series PDUMV30HV2 PDU - Tripp Lite by Eaton 5.8kW Single Phase Local Metered 200 240V Outlets (8 C19 and 40 C13) L6 30P 10 ft. (3.05 m) Cord 0U Vertical TAA 70 in. NEMA L6 30P 8 x IEC 60320 C19, 40 x IEC 60320 C13
Tripp Lite series PDUMV30HV2 PDU - Tripp Lite by Eaton 5.8kW Single Phase Local Metered 200 240V Outlets (8 C19 and 40 C13) L6 30P 10 ft. (3.05 m) Cord 0U Vertical TAA 70 in. NEMA L6 30P 8 x IEC 60320 C19, 40 x IEC 60320 C13 Tripp Lite series PDUMV30HV2 PDU - Tripp Lite by Eaton 5.8kW Single Phase Local Metered 200 240V Outlets (8 C19 and 40 C13) L6 30P 10 ft. (3.05 m) Cord 0U Vertical TAA 70 in. NEMA L6 30P 8 x IEC 60320 C19, 40 x IEC 60320 C13 Tripp Lite series PDUMV30HV2 PDU - Tripp Lite by Eaton 5.8kW Single Phase Local Metered 200 240V Outlets (8 C19 and 40 C13) L6 30P 10 ft. (3.05 m) Cord 0U Vertical TAA 70 in. NEMA L6 30P 8 x IEC 60320 C19, 40 x IEC 60320 C13

Tripp Lite series PDUMV30HV2 PDU - Tripp Lite by Eaton 5.8kW Single Phase Local Metered 200 240V Outlets (8 C19 and 40 C13) L6 30P 10 ft. (3.05 m) Cord 0U Vertical TAA 70 in. NEMA L6 30P 8 x IEC 60320 C19, 40 x IEC 60320 C13

The 70-inch (178-centimeter) PDUMV30HV2 30A 208/240V 5.8kW Single-Phase Metered Power Distribution Unit features 48 outlets for distributing single-phase AC power to rack-mounted equipment, including computers, routers, switches and servers.

Outlets are arranged in two separate load banks, each with 24 outlets (4 C19 and 20 C13), a dedicated 20A circuit breaker and a digital meter that reports the bank's real-time output current in amps. The ammeters let you visually monitor each bank and maintain balanced loads to prevent circuit overloads and downtime due to breakers tripping. Special guards prevent the breakers from tripping accidentally. Outlets, breakers and ammeters are color-coded and labeled for easy identification.

An ideal PDU for server rooms, network closets and data centers, the PDUMV30HV2's all-metal housing comes ready to mount vertically in your rack using the preinstalled 9 mm buttons or the included hardware. The NEMA L6-30P input plug with 10-foot (3-meter) cord connects to your facility's compatible AC power source, generator or protected UPS. Included C20 and C14 plug-lock inserts connect to your components' plugs to ensure they remain connected and continuously powered. Use the included ground screw to connect any equipment that requires a chassis ground.

More from the Manufacturer

Manufacturer: TRIPP LITE SUPPORT
MPN: PDUMV30HV2
Availability: Special Order
Condition: New
CA Proposition 65: None
$567.08
Add to Wishlist

Product Description

Technical Information
  • Plug/Connector Type:
    NEMA L6-30P
  • Receptacle Type:
    IEC 60320 C13, IEC 60320 C19
  • Receptacle Detail:
    40 x IEC 60320 C13, 8 x IEC 60320 C19
  • Protection Type:
    Overload Protection
Power Description
  • Input Voltage:
    230 V AC
  • Output Voltage:
    230 V AC
  • Power Rating (Watt):
    5800 W
  • Input Current:
    30 A
Physical Characteristics
  • Mounting Orientation:
    Vertical
  • Rack Height:
    0U
  • Height:
    70"
  • Width:
    2.2"
  • Depth:
    2.5"
  • Weight (Approximate):
    12.35 lb
Miscellaneous
  • Country of Origin:
    Taiwan
  • TAA Compliant:
    Yes
  • Environmentally Friendly:
    Yes
  • Environmental Compliance:
    Restriction of Hazardous Substances (RoHS)

OVERVIEW
PDU Type
Metered
OUTPUT
Frequency Compatibility
50 / 60 Hz
Output Capacity Details
5.8kW (240V), 5kW (208V), 4.8kW (200V) total capacity / 30A max (Agency de-rated to 24A), 20A max per breakered outlet bank 16A max per C19 outlet 12A max per C13 outlet
Output Receptacles
(40) C13 (8) C19
Output Nominal Voltage
200 208 240
Overload Protection
Two 20A breakers protect 24 outlets each
INPUT
PDU Input Voltage
200 208 240
Recommended Electrical Service
30A 208/240V
Maximum Input Amps
30
Maximum Input Amps Details
Agency de-rated to 24A continuous
PDU Plug Type
NEMA L6-30P
Input Phase
Single-Phase
Input Cord Length (ft.)
10
USER INTERFACE, ALERTS AND CONTROLS
Reported Load Segments
Supports local monitoring of output current for each output load bank Outlets, circuit breakers and current meters are color-coded and labeled for easy identification (Black: 20A Bank 1 / Gray: 20A Bank 2)
Front Panel LCD Display
Set of two digital current meters report output current in two segments
Front Panel LEDs
n/a
Switches
n/a
PHYSICAL
Form Factors Supported
0u vertical installation in equipment racks, plus under-counter and wallmount
Material of Construction
Metal
PDU Form Factor
Vertical (0U)
ENVIRONMENTAL
Operating Temperature Range
32 to122F (0 to 50C)
Storage Temperature Range
-30oC to +60oC (-22oF to +140oF)
Relative Humidity
5-95% non-condensing
CERTIFICATIONS
Certifications
Tested to UL/CAN 60950-1 (USA, Canada), NOM (Mexico), FCC Class A (Emissions), ROHS Compliant, TAA Compliant
Item Dimension (L"xW"xH")
7 x 10 x 76

Weight
39 lbs

Warranty Information
2-year limited warranty